NiceDigz Rentals · Macon, Georgia

HVAC Bid Packet: The Terry & The BillE

Two ducted mini-split systems for a block duplex, about 575 sq ft per unit.

What I'm asking for

Please review this preliminary layout and give me a quote to supply and install two Senville concealed-duct heat pumps, one per apartment.

I've sized the ducts and grilles as a starting point only. I'd like your load calc and your answers to the 12 questions below. A quick reply by number (for example, "Q5: go 8-inch") is perfect.

You don't need to read the manuals. The pages that matter are linked under Key manual pages.

Contact: Andy Myers  |  478-978-2037  |  andy@nicedigz.com 

Project at a glance

LocationMacon, GA
BuildingConcrete block, stucco exterior, slab
Units2 apartments, about 575 sq ft each
Equipment2 × Senville SENA-12HF-ID
Capacity12,000 BTU/h cool · 12,500 heat
RefrigerantR-454B
Ceilings8 ft, attic above
Target comfort70–72°F, 1–2 guests

Floor plan & proposed layout

Duplex floor plan with proposed air handlers, supply runs and returns for the BillE side (blue) and Terry side (maroon)
BillE side (H1) Terry side (H2) H = air handler · R1 = central return · R2 = bedroom jumper Dotted line = line set to condenser

Tap the image to zoom, or open the full-resolution PDF.

Equipment (per apartment)

SpecSENA-12HF-ID
Cooling capacity12,000 BTU/h (range 3,400–13,500)
Heating capacity12,500 BTU/h
Efficiency20 SEER2
Indoor airflow (Turbo/High/Med/Low)400 / 324 / 265 / 177 CFM
Indoor unit size27.56" W × 19.92" D × 7.87" H
OrientationHorizontal only
Electrical208/230 V, single-phase
Proposed line set25 ft (factory charge covers up to 25 ft; max 82 ft, max drop 49.2 ft)

Duct layout & airflow targets

ComponentBillETerry
Air handlerH1, centralH2, central
Living room supply8" R-8 flex · 225 CFM8" R-8 flex · 225 CFM
Bedroom supply7" R-8 flex · 175 CFM7" R-8 flex · 175 CFM
Total supply400 CFM400 CFM
R1 central return16"×20" grille · 14" R-8 flex · 400 CFM16"×20" grille · 14" R-8 flex · 400 CFM
R2 bedroom jumper (passive)10" R-8 flex · 2 × 12"×12" grilles · 175 CFM10" R-8 flex · 2 × 12"×12" grilles · 175 CFM
Supply plenumCustom, 2 outletsCustom, 2 outlets
Return plenumCustom, 1 connectionCustom, 1 connection
CondenserBehind bathroomBehind bathroom

All sizes are preliminary. The 400 CFM targets assume the unit's maximum listed airflow, so real airflow will likely be lower once duct resistance is counted. The 7" bedroom supply may need upsizing. Final sizing should follow your load calc and the fan curves (service manual p.22–23).

How the returns work

Site conditions

Questions for you

  1. Does the 12,000 BTU Senville meet the calculated heating and cooling loads for each apartment?
  2. What airflow can the air handler actually deliver at this duct system's external static pressure?
  3. Are the 14" central return duct and 16"×20" return grille sized right?
  4. Is the 10" bedroom jumper big enough to move the bedroom supply air without excess pressure or noise?
  5. Are the 8" living room and 7" bedroom supplies enough, or should the bedroom supply go up?
  6. Would a two-outlet supply plenum be better than a four-outlet one with the unused outlets capped?
  7. Can the supply and return plenums be fabricated locally to fit the Senville air handler?
  8. Does the central air handler location leave enough horizontal clearance for maintenance, filter changes and condensate drainage?
  9. Will 25 ft line sets reach both condensers with proper routing and allowable elevation differences?
  10. What filter setup gives good airflow without too much pressure drop?
  11. What condensate overflow protection is right for these air handler locations?
  12. Can the finished system be commissioned with measured supply airflow, total external static pressure, and bedroom pressure with the door closed?